Chapter 19 Concrete
Italics are used for text within Sections 1903 through 1905 of this code to indicate provisions that differ from ACI 318.
User notes:
About this chapter: Chapter 19 provides minimum accepted practices for the design and construction of buildings and structural components using concrete—both plain and reinforced. Chapter 19 relies primarily on the reference to American Concrete Institute (ACI) 318, Building Code Requirements for Structural Concrete. Structural concrete must be designed and constructed to comply with this code and all listed standards. There are also specific provisions addressing concrete slabs and shotcrete.
Code development reminder: Code change proposals to this chapter will be considered by the IBC—Structural Code Development Committee during the 2019 (Group B) Code Development Cycle. See explanation on page iv.
Section 1901 General
1901.1 Scope
The provisions of this chapter shall govern the materials, quality control, design and construction of concrete used in structures.
1901.2 Plain and Reinforced Concrete
Structural concrete shall be designed and constructed in accordance with the requirements of this chapter and ACI 318 as amended in Section 1905 of this code. Except for the provisions of Sections 1904 and 1907, the design and construction of slabs on grade shall not be governed by this chapter unless they transmit vertical loads or lateral forces from other parts of the structure to the soil. Precast concrete diaphragms in buildings assigned to Seismic Design Category C, D, E or F shall be designed in accordance with the requirements of ASCE 7, Section 14.2.4.
1901.3 Anchoring to Concrete
Anchoring to concrete shall be in accordance with ACI 318 as amended in Section 1905, and applies to cast-in (headed bolts, headed studs and hooked J- or L-bolts), post-installed expansion (torque-controlled and displacement-controlled), undercut and adhesive anchors.
1901.4 Composite Structural Steel and Concrete Structures
Systems of structural steel acting compositely with reinforced concrete shall be designed in accordance with Section 2206 of this code.
1901.5 Construction Documents
The construction documents for structural concrete construction shall include:
- The specified compressive strength of concrete at the stated ages or stages of construction for which each concrete element is designed.
- The specified strength or grade of reinforcement.
- The size and location of structural elements, reinforcement and anchors.
- Provision for dimensional changes resulting from creep, shrinkage and temperature.
- The magnitude and location of prestressing forces.
- Anchorage length of reinforcement and location and length of lap splices.
- Type and location of mechanical and welded splices of reinforcement.
- Details and location of contraction or isolation joints specified for plain concrete.
- Minimum concrete compressive strength at time of posttensioning.
- Stressing sequence for posttensioning tendons.
- For structures assigned to Seismic Design Category D, E or F, a statement if slab on grade is designed as a structural diaphragm.
1901.6 Special Inspections and Tests
Special inspections and tests of concrete elements of buildings and structures and concreting operations shall be as required by Chapter 17.
Section 1902 Definitions
1902.1 General
The words and terms defined in ACI 318 shall, for the purposes of this chapter and as used elsewhere in this code for concrete construction, have the meanings shown in ACI 318 as modified by Section 1905.1.1.
Section 1903 Specifications for Tests and Materials
1903.1 General
Materials used to produce concrete, concrete itself and testing thereof shall comply with the applicable standards listed in ACI 318.
Exception: The following standards as referenced in Chapter 35 shall be permitted to be used.
- ASTM C150
- ASTM C595
- ASTM C1157
1903.2 Special Inspections
Where required, special inspections and tests shall be in accordance with Chapter 17.
1903.3 Glass Fiber-Reinforced Concrete
Glass fiber-reinforced concrete (GFRC) and the materials used in such concrete shall be in accordance with the PCI MNL 128 standard.
1903.4 Flat Wall Insulating Concrete Form (ICF) Systems
Insulating concrete form material used for forming flat concrete walls shall conform to ASTM E2634.
Section 1904 Durability Requirements
1904.1 Structural Concrete
Structural concrete shall conform to the durability requirements of ACI 318.
Exception: For Group R-2 and R-3 occupancies not more than three stories above grade plane, the specified compressive strength, f´c, for concrete in basement walls, foundation walls, exterior walls and other vertical surfaces exposed to the weather shall be not less than 3,000 psi (20.7 MPa).
1904.2 Nonstructural Concrete
The registered design professional shall assign nonstructural concrete a freeze-thaw exposure class, as defined in ACI 318, based on the anticipated exposure of nonstructural concrete. Nonstructural concrete shall have a minimum specified compressive strength, f´c, of 2,500 psi (17.2 MPa) for Class F0; 3,000 psi (20.7 MPa) for Class F1; and 3,500 psi (24.1 MPa) for Classes F2 and F3. Nonstructural concrete shall be air entrained in accordance with ACI 318.
Section 1905 Modifications to ACI 318
1905.1 General
The text of ACI 318 shall be modified as indicated in Sections 1905.1.1 through 1905.1.8.
1905.1.1 ACI 318, Section 2.3
Modify existing definitions and add the following definitions to ACI 318, Section 2.3.
DESIGN DISPLACEMENT. Total lateral displacement expected for the design-basis earthquake, as specified by Section 12.8.6 of ASCE 7.
DETAILED PLAIN CONCRETE STRUCTURAL WALL. A wall complying with the requirements of Chapter 14, including 14.6.2.
ORDINARY PRECAST STRUCTURAL WALL. A precast wall complying with the requirements of Chapters 1 through 13, 15, 16 and 19 through 26.
ORDINARY REINFORCED CONCRETE STRUCTURAL WALL. A cast-in-place wall complying with the requirements of Chapters 1 through 13, 15, 16 and 19 through 26.
ORDINARY STRUCTURAL PLAIN CONCRETE WALL. A wall complying with the requirements of Chapter 14, excluding 14.6.2.
SPECIAL STRUCTURAL WALL. A cast-in-place or precast wall complying with the requirements of 18.2.4 through 18.2.8, 18.10 and 18.11, as applicable, in addition to the requirements for ordinary reinforced concrete structural walls or ordinary precast structural walls, as applicable. Where ASCE 7 refers to a "special reinforced concrete structural wall," it shall be deemed to mean a "special structural wall."
1905.1.2 ACI 318, Section 18.2.1
Modify ACI 318 Sections 18.2.1.2 and 18.2.1.6 to read as follows:
- 18.2.1.2 — Structures assigned to Seismic Design Category A shall satisfy requirements of Chapters 1 through 17 and 19 through 26; Chapter 18 does not apply. Structures assigned to Seismic Design Category B, C, D, E or F shall satisfy 18.2.1.3 through 18.2.1.7, as applicable. Except for structural elements of plain concrete complying with Section 1905.1.7 of the International Building Code, structural elements of plain concrete are prohibited in structures assigned to Seismic Design Category C, D, E or F.
18.2.1.6 — Structural systems designated as part of the seismic force-resisting system shall be restricted to those permitted by ASCE 7. Except for Seismic Design Category A, for which Chapter 18 does not apply, the following provisions shall be satisfied for each structural system designated as part of the seismic force-resisting system, regardless of the seismic design category :
- Ordinary moment frames shall satisfy 18.3.
- Ordinary reinforced concrete structural walls and ordinary precast structural walls need not satisfy any provisions in Chapter 18.
- Intermediate moment frames shall satisfy 18.4.
- Intermediate precast structural walls shall satisfy 18.5.
- Special moment frames shall satisfy 18.6 through 18.9.
- Special structural walls shall satisfy 18.10.
- Special structural walls constructed using precast concrete shall satisfy 18.11.
1905.1.3 ACI 318, Section 18.5
Modify ACI 318, Section 18.5 by adding new Section 18.5.2.2 and renumbering existing Sections 18.5.2.2 and 18.5.2.3 to become 18.5.2.3 and 18.5.2.4, respectively.
- 18.5.2.2 — Connections that are designed to yield shall be capable of maintaining 80 percent of their design strength at the deformation induced by the design displacement or shall use Type 2 mechanical splices.
- 18.5.2.3 — Elements of the connection that are not designed to yield shall develop at least 1.5 Sy.
- 18.5.2.4 — In structures assigned to SDC D, E or F, wall piers shall be designed in accordance with 18.10.8 or 18.14 in ACI 318.
1905.1.4 ACI 318, Section 18.11
Modify ACI 318, Section 18.11.2.1 to read as follows:
- 18.11.2.1 — Special structural walls constructed using precast concrete shall satisfy all the requirements of 18.10 for cast-in-place special structural walls in addition to 18.5.2.
1905.1.5 ACI 318, Section 18.13.1.1
Modify ACI 318, Section 18.13.1.1 to read as follows:
- 18.13.1.1 — Foundations resisting earthquake-induced forces or transferring earthquake-induced forces between a structure and ground shall comply with the requirements of 18.13 and other applicable provisions of ACI 318unless modified by Chapter 18 of theInternational Building Code.
1905.1.6 ACI 318, Section 14.6
Modify ACI 318, Section 14.6 by adding new Section 14.6.2 to read as follows:
14.6.2 — Detailed plain concrete structural walls.
14.6.2.1 — Detailed plain concrete structural walls are walls conforming to the requirements of ordinary structural plain concrete walls and 14.6.2.2.
- Vertical reinforcement of at least 0.20 square inch (129 mm 2 ) in cross-sectional area shall be provided continuously from support to support at each corner, at each side of each opening and at the ends of walls. The continuous vertical bar required beside an opening is permitted to substitute for one of the two No. 5 bars required by 14.6.1.
- Horizontal reinforcement at least 0.20 square inch (129 mm 2 ) in cross-sectional area shall be provided:
- Continuously at structurally connected roof and floor levels and at the top of walls.
- At the bottom of load-bearing walls or in the top of foundations where doweled to the wall.
- At a maximum spacing of 120 inches (3048 mm).
1905.1.7 ACI 318, Section 14.1.4
Delete ACI 318, Section 14.1.4 and replace with the following:
14.1.4 — Plain concrete in structures assigned to Seismic Design Category C, D, E or F.
- Structural plain concrete basement, foundation or other walls below the base as defined in ASCE 7 are permitted in detached one- and two-family dwellings three stories or less in height constructed with stud-bearing walls. In dwellings assigned to Seismic Design Category D or E, the height of the wall shall not exceed 8 feet (2438 mm), the thickness shall be not less than 7 1 /2 inches (190 mm), and the wall shall retain no more than 4 feet (1219 mm) of unbalanced fill. Walls shall have reinforcement in accordance with 14.6.1.
- Isolated footings of plain concrete supporting pedestals or columns are permitted, provided the projection of the footing beyond the face of the supported member does not exceed the footing thickness.
Exception: In detached one- and two-family dwellings three stories or less in height, the projection of the footing beyond the face of the supported member is permitted to exceed the footing thickness.
- In Seismic Design Categories A, B and C, detached one- and two-family dwellings three stories or less in height constructed with stud-bearing walls are permitted to have plain concrete footings without longitudinal reinforcement.
- For foundation systems consisting of a plain concrete footing and a plain concrete stemwall, a minimum of one bar shall be provided at the top of the stemwall and at the bottom of the footing.
- Where a slab on ground is cast monolithically with the footing, one No. 5 bar is permitted to be located at either the top of the slab or bottom of the footing.
1905.1.8 ACI 318, Section 17.2.3
Modify ACI 318 Sections 17.2.3.4.2, 17.2.3.4.3(d) and 17.2.3.5.2 to read as follows:
17.2.3.4.2 — Where the tensile component of the strength-level earthquake force applied to anchors exceeds 20 percent of the total factored anchor tensile force associated with the same load combination, anchors and their attachments shall be designed in accordance with 17.2.3.4.3. The anchor design tensile strength shall be determined in accordance with 17.2.3.4.4.
Exception: Anchors designed to resist wall out-of-plane forces with design strengths equal to or greater than the force determined in accordance with ASCE 7 Equation 12.11-1 or 12.14-10 shall be deemed to satisfy Section 17.2.3.4.3(d).
17.2.3.5.2 — Where the shear component of the strength-level earthquake force applied to anchors exceeds 20 percent of the total factored anchor shear force associated with the same load combination, anchors and their attachments shall be designed in accordance with 17.2.3.5.3. The anchor design shear strength for resisting earthquake forces shall be determined in accordance with 17.5.
Exceptions:
- For the calculation of the in-plane shear strength of anchor bolts attaching wood sill plates of bearing or nonbearing walls of light-frame wood structures to foundations or foundation stem walls, the in-plane shear strength in accordance with 17.5.2 and 17.5.3 need not be computed and 17.2.3.5.3 shall be deemed to be satisfied provided all of the following are met:
- The allowable in-plane shear strength of the anchor is determined in accordance with ANSI/AWC NDS Table 12E for lateral design values parallel to grain.
- The maximum anchor nominal diameter is 5 /8 inch (16 mm).
- Anchor bolts are embedded into concrete a minimum of 7 inches (178 mm).
- Anchor bolts are located a minimum of 1 3 /4 inches (45 mm) from the edge of the concrete parallel to the length of the wood sill plate.
- Anchor bolts are located a minimum of 15 anchor diameters from the edge of the concrete perpendicular to the length of the wood sill plate.
- The sill plate is 2-inch (51 mm) or 3-inch (76 mm) nominal thickness.
- The maximum anchor nominal diameter is 5 /8 inch (16 mm).
- Anchors are embedded into concrete a minimum of 7 inches (178 mm).
- Anchors are located a minimum of 1 3 /4 inches (45 mm) from the edge of the concrete parallel to the length of the track.
- Anchors are located a minimum of 15 anchor diameters from the edge of the concrete perpendicular to the length of the track.
- The track is 33 to 68 mil (0.84 mm to 1.73 mm) designation thickness.
Allowable in-plane shear strength of exempt anchors, parallel to the edge of concrete, shall be permitted to be determined in accordance with AISI S100 Section E3.3.1.